ABB 07BR61 R1 (GJV3074376R1) – CS31 Bus Repeater/Isolator for Extending and Protecting Field Networks

1 Brand: ABB
2 Model: 07BR61 R1 GJV3074376R1
3 Quality: Original module
4 Warranty: 1 year
5 Delivery time: 1 week in stock
6 Condition: New/Used
7 Shipping method: DHL/UPS

contact qrcode

Need help?
Email: sales@fyplc.cn
Tel/WhatsApp: +86 173 5088 0093

Description

ABB 07BR61 R1 (GJV3074376R1) – CS31 Bus Repeater/Isolator for Extending and Protecting Field Networksabb_07br61r1_gjv3074376r1_motion_controller

The ABB 07BR61 R1, order code GJV3074376R1, is a dedicated CS31 bus repeater/isolator used in ABB AC31/Procontic control systems to extend bus distance, segment the network, and improve noise immunity. From my experience, teams add this module when a single CS31 segment grows too long or when galvanic isolation between noisy and clean areas is needed. You might notice that it typically stabilizes communication in facilities with heavy drives, long cable runs, or mixed grounding conditions.

Company’s Order Placement Process and Guarantees

  • Warranty: 365 days
  • Lead time: 1 week if in stock; no more than 1 month at the latest
  • Payment: 50% advance payment; full payment prior to delivery
  • Express delivery: FedEx, UPS, DHL

Key Features

  • CS31 Segment Extension – Extends bus length and allows more flexible topology by bridging two RS‑485-based CS31 segments.
  • Galvanic Isolation – Typically isolates segments to reduce ground loop issues and protect upstream controllers from transients.
  • Noise Immunity – Designed for industrial EMC environments; in many cases improves stability near VFDs and heavy machinery.
  • Status LEDs – Quick visual diagnostics for power and bus activity, helping maintenance teams spot line faults faster.
  • DIN-Rail Mounting – Compact footprint for panel builders; straightforward to drop into existing AC31 panels.
  • Wiring Flexibility – Screw-terminal connections for shielded twisted-pair CS31 cabling, commonly used on plant floors.
  • Backward Compatibility – Typically used alongside AC31 CPUs and I/O nodes without firmware changes to existing devices.

Technical Specifications

Brand / Model ABB 07BR61 R1 (Order code: GJV3074376R1)
HS Code 8537.10 (Control panels/consoles for electric control or distribution; final classification may vary by destination)
Power Requirements 24 VDC nominal (typical), low power consumption suitable for panel power rails
Signal I/O Types Differential RS‑485 (CS31 bus) ports for segment‑to‑segment repeating/isolating
Communication Interfaces CS31 bus; screw terminals for shielded twisted-pair
Installation Method DIN rail (TH35) mounting in control cabinet
Operating Temperature 0 to +55 °C typical for panel-mounted modules
Dimensions & Weight Compact DIN-rail form factor; typically a single-module width; approx. 0.2–0.3 kg

Application Fields

The 07BR61 R1 is commonly used in AC31/Procontic-based lines for discrete manufacturing, material handling, metals, and water/wastewater. In many cases it sits between long conveyor sections to re‑clock and isolate the CS31 bus, or at building transitions where grounding differs. One maintenance engineer told us they added this repeater near a bank of VFDs and saw immediate improvement in bus stability during motor acceleration.

Advantages & Value

  • Reliability – Isolation and regeneration typically reduce communication errors and downtime.
  • Compatibility – Works with established ABB AC31 nodes and wiring practices; no major program changes.
  • Cost Control – Lets you extend existing infrastructure rather than replacing long bus runs or adding new panels.
  • Maintainability – Status LEDs and clear terminal labeling speed up troubleshooting.
  • Lifecycle Support – Suitable as a maintenance replacement part to keep legacy cells productive.

Installation & Maintenance

  • Cabinet & Mounting – Install on TH35 DIN rail inside a ventilated control cabinet. Keep high‑power cables segregated where possible.
  • Power Wiring – Supply clean 24 VDC. Bond protective earth per panel standards to reduce common‑mode noise.
  • Bus Wiring – Use shielded twisted pair for CS31. Maintain consistent polarity (A/B). Terminate segments appropriately (typically 120 Ω at each segment end).
  • Grounding & Shielding – Connect shields at one end or per site EMC policy to avoid loops. The repeater isolation helps when ground potentials differ.
  • Distance & Topology – Keep total segment lengths within CS31 limits; add repeaters at logical breakpoints or noise boundaries.
  • Routine Checks – Periodically inspect terminal tightness, look for LED alarms, and clean dust. Firmware updates are rarely required for this type of module, but keep site documentation up to date.
  • Spares Strategy – From my experience, plants keep at least one spare per area to shorten MTTR during unplanned stops.

Quality & Certifications

  • Manufacturer quality system: ISO 9001
  • CE marked for EMC and low-voltage directives (typical for this series)
  • UL/CSA suitability depends on panel listing; many ABB AC31 modules are UL Recognized
  • RoHS compliance for most current-production or service parts
  • Manufacturer’s warranty support plus our 365-day warranty

Related and Supporting Components

  • AC31 CPUs (e.g., 07KR-series) and communication modules (e.g., 07KT-series) used on CS31 networks
  • 24 VDC panel power supplies and surge protection devices for stable bus operation
  • Shielded twisted-pair cabling and terminal blocks for CS31 wiring practices

If you’re extending an existing AC31 line or isolating a noisy zone, the ABB 07BR61 R1 seems to be a sensible drop‑in. We typically review the bus topology and termination first; a quick look at shield connections and segment lengths often uncovers easy wins before commissioning.