Description
Basic Information
- Model: MVI56-MNET
- Brand: ProSoft Technology (Rockwell Automation official partner)
- Full Name: Modbus TCP/IP Client/Server Communication Interface Module
- Compatible Host: Allen‑Bradley 1756 ControlLogix PLC chassis (occupies single slot)
- Warranty: 1 Year
- Lifecycle: Classic legacy model, upgraded version is MVI56E-MNET; widely used for old ControlLogix system maintenance replacement
1. Core Technical Specifications
1.1 Communication Performance
- Ethernet Port
- Single 10/100Mbps auto-negotiation RJ45 Ethernet port, electrical isolation protection
- Protocol: Standard Modbus TCP/IP (fully compliant with Modbus IDA specification)
- Master & Slave Capacity
- Modbus TCP Client (Master): Up to 32 independent TCP client connections (poll 32 sets of Modbus TCP slave devices simultaneously)
- Modbus TCP Server (Slave): Up to 8 server connections (allow upper DCS/SCADA/HMI to read/write PLC data via Modbus TCP)
- Supported Modbus function codes: 01/02/03/04/05/06/15/16/22/23 full set of standard codes for coils, discrete inputs, holding registers, input registersProSoft Te…
- Data Mapping Capacity
- Max total register database: 10,000 16-bit Modbus registers (upload/download between module and ControlLogix controller)
- Data interaction: Transparent data exchange with Logix tags via backplane CIP bus, maximum 8192 bytes input + 8192 bytes output data buffer

1.2 Power & Mechanical Parameters
- Backplane power consumption: 800mA @ 5VDC, 3mA @ 24VDC
- Dimensions: 147mm × 98mm × 64mm, Net weight ≈ 0.32kg
- Protection Class: IP20 (installed inside ControlLogix control cabinet only)
- Mounting: Standard 1756 single-slot plug-in structure, supports local chassis or remote ControlNet/EtherNet/IP distributed rack installation
1.3 Environmental & Industrial Protection
- Operating temperature: 0°C ~ +60°C
- Storage temperature: -40°C ~ +85°C
- Humidity: 5%–95% non-condensing
- Shock resistance: 30g operating, 50g non-operating; Vibration: 5g (10Hz–150Hz)
- Certifications: UL/cUL Class I Div 2 hazardous area approval, CE, RoHS
- Onboard diagnostics: LED indicators for Module Status, Network Status, Ethernet Link/Activity, fault alarm; built-in web server for remote parameter checking and troubleshooting
2. Product Overview
The MVI56-MNET is a rack-mounted dedicated communication coprocessor module embedded directly into the ControlLogix PLC backplane, the most mainstream solution for Rockwell Logix platform to connect Modbus TCP Ethernet devices.








Reviews
There are no reviews yet.