PLX31-EIP-MBS ProSoft Technology EtherNet/IP to Modbus Serial Gateway

$2,550.00

  • Model: PLX31-EIP-MBS
  • Brand: ProSoft Technology (USA, leading industrial protocol gateway manufacturer)
  • Full Function: Bidirectional protocol conversion gateway between EtherNet/IP industrial Ethernet and Modbus serial bus (RTU/ASCII)
  • Warranty: 1 Year
Categories: Tags: SKU: PLX31-EIP-MBS
Lily

Need help?
Email: sales@fyplc.cn
Tel/WhatsApp: +86 153 5945 8915

Description

PLX31-EIP-MBS ProSoft Technology EtherNet/IP to Modbus Serial Gateway

Basic Information

  • Model: PLX31-EIP-MBS
  • Brand: ProSoft Technology (USA, leading industrial protocol gateway manufacturer)
  • Full Function: Bidirectional protocol conversion gateway between EtherNet/IP industrial Ethernet and Modbus serial bus (RTU/ASCII)
  • Warranty: 1 Year
  • Core Matching System: Rockwell Allen‑Bradley ControlLogix / CompactLogix / Micro800 EtherNet/IP PLC platform

1. Detailed Technical Specifications

1.1 Communication Interfaces

EtherNet/IP Side

  • Dual RJ45 10/100Mbps auto-negotiation Ethernet ports (switch built-in, daisy chain cabinet wiring)
  • Isolation: 1500Vrms electrical isolation for Ethernet circuit
  • Support EtherNet/IP Class 1 real-time I/O connection and Class 3 message connection
  • Embedded EDS file, directly imported into RSLogix 5000/Studio 5000 for zero-drag configuration
  • Max data exchange: Up to 1440 bytes input + 1440 bytes output; supports up to 10,000 16-bit Modbus registers mapping
  • PROSOFT_PLX32-EIP-SIE_5

Modbus Serial Side

  • 1 configurable serial terminal port: RS232 / RS422 / RS485 hardware switchable
  • Supported protocols: Modbus RTU (CRC16), Modbus ASCII (LRC)
  • Baud rate range: 110 bps ~ 115200 bps freely set
  • Parity: None / Odd / Even; Data bits 7/8, Stop bits 1/2
  • Max 32 Modbus slave nodes on RS485 bus, slave address range 1~247
  • Complete Modbus function code support (01/02/03/04/05/06/15/16 etc. for coils, discrete inputs, holding registers, input registers)

1.2 Power & Environmental

  • Power input: 10~36VDC wide DC, rated 24VDC 300mA, max 610mA
  • Operating temperature: -25°C ~ +70°C
  • Storage temperature: -40°C ~ +80°C
  • Humidity: 5%–95% non-condensing
  • Mounting: Standard 35mm DIN rail vertical/horizontal installation
  • Certifications: UL/cUL Class I Div 2, CE, ATEX Zone 2, ODVA EtherNet/IP certified
  • Extra hardware: Built-in micro SD card slot for configuration file backup & one-click recovery
  • Full LED diagnostic indicators: PWR, ERR, FLT, MS, NS, Ethernet Link/Act, Serial TX/RX

1.3 Protection & Performance

  • Onboard ESD, surge, EFT transient suppression circuit
  • Broadcast storm protection for Ethernet port
  • Independent data RPI cycle setting for control and status data to optimize Ethernet bandwidth
  • Web server built-in for remote diagnosis, register monitoring and fault code query