ABB ANR96 Multifunction Power Network Analyzer

$2,355.00

  • Product Model: ANR96
  • Brand: ABB
  • Warranty: One Year
  • Input Voltage: 85‑265 VAC / 85‑265 VDC universal auxiliary supply
  • Operating Temperature: ‑10 °C to +55 °C
Categories: Tags: SKU: ANR96
Lily

Need help?
Email: sales@fyplc.cn
Tel/WhatsApp: +86 153 5945 8915

Description

ABB ANR96 Multifunction Power Network Analyzer

Technical Specifications

  • Product Model: ANR96
  • Brand: ABB
  • Warranty: One Year
  • Input Voltage: 85‑265 VAC / 85‑265 VDC universal auxiliary supply
  • Operating Temperature: ‑10 °C to +55 °C
  • Storage Temperature: ‑20 °C to +70 °C
  • Response Time: <400 ms measurement refresh cycle
  • Protection Class: IP52 (front panel; IP20 rear terminal area)
  • Accuracy Class: Class 0.5 for voltage/current; class 1 for power‑energy measurement
  • Output Frequency: 45‑65 Hz fundamental grid frequency monitoring
  • Rated Current Range: 0‑5 A nominal current transformer input
  • Communication Interface: Isolated RS232 / RS485; optional Ethernet / PROFIBUS‑DP
  • Supported Protocols: Modbus‑RTU, ASCII; Modbus‑TCP (LAN variant), PROFIBUS‑DP‑V0 (PRF variant)
  • Overload Capacity: Continuous 750 VAC voltage withstand; 2× nominal current short‑term overload
  • Dimensions: 96 mm × 96 mm × 110 mm panel‑mount form factor

Product Overview

The ANR96 is a panel‑mount multifunction electrical network analyzer built for three‑phase power‑system monitoring within industrial facilities, power‑generation plants and utility substations. It acquires voltage, current, power factor, active/reactive power and energy readings, alongside harmonic‑distortion analysis up to the 31st harmonic, delivering comprehensive visibility over grid‑quality conditions. The integrated backlit graphic LCD and five‑button keypad enable local parameter setup, measured‑value browsing and alarm‑threshold configuration without external software.

This device addresses key electrical‑monitoring challenges: unified multi‑parameter power‑network measurement, harmonic disturbance detection, and seamless data export to DCS/SCADA platforms for energy‑management workflows. Isolated communication ports reduce ground‑loop interference over long‑distance field‑bus wiring. Plant‑electrical engineers, energy‑management technicians and system‑retrofit integrators benefit most. It fits standard 96×96 mm panel cutouts, supports optional digital I/O modules for pulse‑output energy pulsing and alarm‑relay triggering, and serves as drop‑in spare hardware for legacy power‑monitoring installations across process‑industry and power‑plant sites.

abb_uad154a_3bhe026866r0101_control_module


Key Application Notes

  • Accepts voltage‑transformer and current‑transformer secondary signals; not designed for direct high‑voltage connection
  • Base unit provides two opto‑isolated digital inputs; additional I/O and communication functions require option add‑on boards
  • Internal backup battery preserves accumulated energy counters and configuration parameters during supply outages
  • Compliant with IEC 61010‑2 safety standards for industrial electrical‑measurement instruments
  • Measurement data can be logged remotely via Modbus‑RTU/TCP for energy‑audit and power‑quality‑analysis purposes
  • Front‑panel keypad access can be password‑locked to prevent unauthorised parameter modification

Reviews

There are no reviews yet.

Be the first to review “ABB ANR96 Multifunction Power Network Analyzer”

Your email address will not be published. Required fields are marked *

zzfyplc_Lily

Related products