HIMA H51q-HRS B5233-2 fully redundant SIL3 safety controller HIQuad ESD turbine protection

  • Manufacturer: HIMA Paul Hildebrandt (Germany)
  • Model: H51q-HRS, assembly part B5233‑2
  • Device Type: SIL 3 redundant safety controller system
  • Payment Method:T/T
    Payment TermsAdvance: payment / Full payment
Categories: Tags: SKU: H51q-HRS
Lily

Need help?
Email: sales@fyplc.cn
Tel/WhatsApp: +86 153 5945 8915

Description

Product Overview The H51q-HRS is the top-tier fully redundant HIQuad safety programmable electronic system (PES) from HIMA H51q family, built for ESD, burner management, compressor and turbine protection. “HRS” stands for redundant CPU + redundant dual I/O bus architecture. It adopts HIMA’s classic dual-processor compare core; the standby controller takes over seamlessly upon primary failure, while the duplicated I/O bus eliminates single point of failure on the fieldbus side. It supports up to 16 remote I/O sub‑racks and 256 I/O modules, widely deployed in refineries, petrochemical plants and power generation safety loops.

Technical Specifications

  • Manufacturer: HIMA Paul Hildebrandt (Germany)
  • Model: H51q-HRS, assembly part B5233‑2
  • Device Type: SIL 3 redundant safety controller system
  • Safety rating: SIL 3 (IEC 61508 / IEC 61511), TÜV AK 6 certified
  • Architecture: Dual redundant central controllers + dual redundant I/O bus
  • Programming software: ELOP II, conforming to IEC 61131‑3
  • Communication: 10 Mbps Ethernet TCP/IP, PROFIBUS‑DP, Modbus, safe inter-system communication
  • I/O expansion: 1 × 5U main rack, expandable to max 16 × 4U remote I/O racks
  • Power: Dual redundant 24 VDC supply, with fuse monitoring via F7133 power drawer
  • Hot swap: All I/O and power modules support hot replacement without safety trip
  • Diagnostics: Continuous cross-comparison between CPUs, bus error, short circuit, open circuit and supply fault latching
  • Mounting: 19-inch rack, 5U main chassis
  • Operating temperature: −20°C ~ +60°C
  • Humidity: 5% – 95% non‑condensing
  • Weight: Approx. 12.5 kg (complete rack assembly)
  • Certifications: CE, TÜV, FM
  • Feature: Deterministic safety cycle, high diagnostic coverage, vibration-hardened design for critical rotating equipment protection

Differentiation Notes

  • H51q‑M / MS: Single CPU, single I/O bus
  • H51q‑H / HS: Redundant CPU, single I/O bus
  • H51q‑HR / HRS: Redundant CPU + redundant I/O bus; HRS is the fully redundant highest availability version It belongs to legacy HIQuad H51q platform, predecessor of HIMax / HIQuad X. Original production discontinued; available as NOS, refurbished and surplus spare parts for existing safety instrumented system maintenance.

Reviews

There are no reviews yet.

Be the first to review “HIMA H51q-HRS B5233-2 fully redundant SIL3 safety controller HIQuad ESD turbine protection”

Your email address will not be published. Required fields are marked *

zzfyplc_Lily

Related products