ABB REC670 (1MRK002814-AC) – High‑performance bay control IED for substation automation

Brand / ModelABB REC670 – Order code 1MRK002814-AC

HS Code853710 (commonly used for protection & control IEDs; final classification may vary by country)

Power RequirementsTypically 110–250 V DC or 100–240 V AC (alternative 24–60 V DC variants depending on power module)

Dimensions & WeightCompact 19-inch rack/flush-mount style; approx. 4U height; weight varies by I/O configuration

Operating Temperature-25°C to +55°C operation (storage typically up to +70°C)

Signal Input/Output TypesBinary inputs (typ. 24–250 V DC), relay outputs (NO/NC), double-point indications; VT inputs for synchrocheck/voltage measurements

Communication InterfacesIEC 61850 MMS/GOOSE; dual Ethernet with PRP/HSR in many cases; SNTP/IRIG-B; optional IEC 60870-5-104, DNP3, Modbus TCP

Installation MethodPanel/flush mounting in switchgear cabinets; rear terminal wiring; suitable for 19-inch subrack arrangements

Categories: Tags:
contact qrcode

Need help?
Email: sales@fyplc.cn
Tel/WhatsApp: +86 173 5088 0093

Description

ABB REC670 (1MRK002814-AC) – High‑performance bay control IED for substation automation

abb_rec670_1mrk002814-ac_interval_control_device_1

The ABB REC670 is part of the Relion 670 series, built for precise bay control, interlocking, and IEC 61850-based substation automation. The order code 1MRK002814-AC denotes a specific hardware and option combination within the REC670 family—typically configured for robust switchgear control, fast GOOSE messaging, and reliable synchrocheck. One thing I appreciate is how it consolidates bay control logic, measurements, and communications into a single, serviceable unit that fits well in modern and retrofit cubicles.

Company’s Order Placement Process and Guarantees

  • Warranty: 365 days
  • Delivery time: 1 week for in-stock items; no more than one month at the latest
  • Payment terms: 50% advance payment; full payment prior to delivery
  • Express options: FedEx, UPS, DHL

Key Features

  • Bay control and interlocking – Ready-made logic templates with flexible customization to enforce safe switching sequences.
  • Synchrocheck – Voltage inputs allow closing checks across sources, typically reducing mis-operations during energization.
  • IEC 61850 Ed.2 with GOOSE – Fast peer-to-peer signaling and MMS for SCADA; PRP/HSR redundancy on dual Ethernet ports is commonly available.
  • Rich I/O – Galvanically isolated binary inputs, high-duty relay outputs, and double-point indication handling for disconnectors/earthing switches.
  • Event and disturbance records – Millisecond time-stamped SOE and COMTRADE disturbance files streamline fault analysis.
  • Engineering via ABB PCM600 – From my experience, configuration and logic edits are straightforward, which shortens FAT/SAT cycles.
  • Time synchronization – SNTP and IRIG-B help keep records aligned across bays and substations.
  • Modular hardware – Flexible slotting to match feeder, transformer bay, or bus-tie applications; spares stocking becomes simpler.

Technical Specifications

Brand / Model ABB REC670 – Order code 1MRK002814-AC
HS Code 853710 (commonly used for protection & control IEDs; final classification may vary by country)
Power Requirements Typically 110–250 V DC or 100–240 V AC (alternative 24–60 V DC variants depending on power module)
Dimensions & Weight Compact 19-inch rack/flush-mount style; approx. 4U height; weight varies by I/O configuration
Operating Temperature -25°C to +55°C operation (storage typically up to +70°C)
Signal Input/Output Types Binary inputs (typ. 24–250 V DC), relay outputs (NO/NC), double-point indications; VT inputs for synchrocheck/voltage measurements
Communication Interfaces IEC 61850 MMS/GOOSE; dual Ethernet with PRP/HSR in many cases; SNTP/IRIG-B; optional IEC 60870-5-104, DNP3, Modbus TCP
Installation Method Panel/flush mounting in switchgear cabinets; rear terminal wiring; suitable for 19-inch subrack arrangements

Application Fields

  • Transmission and distribution bays (breaker, disconnector, earthing switch control with interlocking)
  • Bus-tie and coupler bays requiring dependable synchrocheck prior to closing
  • Industrial substations—steel, mining, oil & gas—where compact bay control simplifies retrofit projects
  • Renewables and IPP substations integrating IEC 61850 peer-to-peer schemes without hardwiring

Advantages & Value

  • Reliability – Proven Relion 670 platform, event-stable firmware, and fast failover with PRP/HSR reduce single points of failure.
  • Compatibility – Multi-protocol support trims gateway needs and eases SCADA integration in mixed fleets.
  • Lifecycle cost – Modular I/O keeps spares lean and helps standardize across bay types, which in many cases lowers total cost of ownership.
  • Serviceability – Front HMI, clear SOE, and COMTRADE exports shorten fault-finding and outage times.

You might notice that the REC670 scales well from a single feeder to a full yard. A utility client shared that after migrating to IEC 61850 GOOSE on REC670, they eliminated a surprising amount of copper interlocking wiring and cut commissioning hours dramatically.

Installation & Maintenance

  • Cabinet & mounting – Install in a clean, dry switchgear cubicle; allow front access and rear wiring space; maintain ventilation around the unit.
  • Wiring – Use shielded twisted pair for IRIG-B/time sync and Ethernet as per ABB guidelines; keep VT and control wiring segregated; confirm interlocking logic with a formal test plan.
  • Grounding – Bond the IED chassis to the station earth; observe EMC practices to minimize induced noise.
  • Commissioning – Validate GOOSE datasets, time sync (SNTP or IRIG-B), and synchrocheck thresholds; save final PCM600 project backups.
  • Routine maintenance – Periodic logic and settings review, clean front filters/vents, check time sync status, and export SOE/disturbance logs. Firmware updates can be planned during outages to keep functions aligned with fleet standards.

Quality & Certifications

  • CE marked; RoHS compliant
  • Designed and type-tested to relevant IEC standards for protective/measurement IEDs (e.g., IEC 60255 series, EMC/EMI)
  • IEC 61850 conformance for station bus; COMTRADE disturbance records
  • Manufacturer’s warranty: 12 months (as listed above)

Supporting Components (commonly paired)

  • ABB RTXP test switches (for safe secondary injection and isolation during maintenance)
  • IRIG-B time source or GPS clock for precise station-wide time alignment
  • Industrial Ethernet switches with PRP/HSR support for network redundancy
Note: REC670 configurations are highly option-dependent. The code 1MRK002814-AC identifies a specific build; if you share your bay scheme (breaker/disconnector count, VT availability, protocol needs), I can validate I/O cards, power module range, and firmware package before shipment.