ABB RET620 – Transformer protection and control relay for 2- or 3‑winding power transformersRET620

The ABB RET620 is a Relion 620‑series protection and control IED designed specifically for power transformers. From my experience, it’s a solid fit for utilities, IPPs, and industrial substations that want dependable transformer differential protection with modern IEC 61850 communications and straightforward HMI. One thing I appreciate is how it handles multi‑winding configurations and adds practical extras like disturbance recording and flexible logic without turning commissioning into a science project.

Order Placement Process and Guarantees

  • Warranty: 365 days
  • Delivery time: 1 week if in stock; no more than 1 month at the latest
  • Payment: 50% advance payment; full payment prior to delivery
  • Express options: FedEx, UPS, DHL

You might notice that orders go faster when we receive the variant code and desired communication options upfront (for example Ethernet + IEC 61850, or serial + Modbus). That typically shortens configuration and testing on our side.

Key Features

  • Transformer differential (87T) – Sensitive and fast protection for 2‑ or 3‑winding transformers with stabilized algorithms to ride through inrush and CT errors.
  • Restricted earth fault (64REF) – High‑sensitivity protection for internal ground faults, in many cases enabling faster clearance than plain overcurrent.
  • Backup protections – Phase/earth overcurrent (50/51/50N/51N), thermal overload (49), over/under‑voltage (59/27), frequency (81), and breaker failure (50BF) to cover most feeder/transformer contingencies.
  • Flexible I/O and logic – Configurable binary I/O and IEC 61131‑style logic blocks streamline interlocking and scheme logic without extra hardwiring.
  • IEC 61850 with GOOSE – Fast peer‑to‑peer messaging for trip and interlocking; seems to be the preferred route for reducing copper wiring in new builds.
  • Disturbance and event records – COMTRADE disturbance files and detailed event logs make fault analysis faster and more transparent for O&M teams.
  • Intuitive HMI – Front panel with clear single‑line views and LEDs; operators typically find status checks and manual controls effortless.
  • Cybersecurity basics covered – Role‑based access, password protection, and audit trails align with common utility requirements.
  • PCM600 engineering tool – Parameterization, logic, and IED management through ABB’s PCM600 keep lifecycle work consistent across Relion devices.

Technical Specifications

Brand / Model ABB RET620 (Relion 620 series) – Transformer Protection and Control IED
HS Code 8536.49 – Relays for a voltage exceeding 60 V (reference classification for protection relays)
Power Requirements Auxiliary supply typically 24–250 V DC or 100–240 V AC, 50/60 Hz (wide‑range universal supply)
Operating Temperature −40 to +55 °C (typical for Relion 620‑series devices)
Signal I/O Types CT inputs (1 A / 5 A), VT inputs (100/110 V); configurable binary inputs/outputs; trip and alarm contacts
Protection Functions 87T, 64REF, 50/51/50N/51N, 49, 59/27, 81, 50BF; plus supervision and logic per model variant
Communication Interfaces Ethernet 100Base‑TX (IEC 61850 Ed.2 with GOOSE); option‑dependent Modbus TCP/DNP3; serial RS‑485/RS‑232 for Modbus RTU or IEC 60870‑5‑103; SNTP time sync (IRIG‑B option on some variants)
Dimensions & Weight Compact 620‑series flush‑mount case; panel cut‑out per ABB drawing; weight varies with I/O modules (approx. 3–4 kg)
Installation Method Flush‑mount on switchgear panel/door; rear terminal blocks; grounding per ABB guidelines; wiring via ring/fork lugs as specified

Where it typically fits

– 110/132 kV and 220/230 kV substations protecting primary transformers with IEC 61850 station bus.

– Industrial plants (steel, mining, oil & gas) where transformer differential plus robust backup protection is needed on limited space.

A utility client recently swapped aging electromechanical relays for RET620 on a 50 MVA transformer. Fault event retrieval through COMTRADE shortened their root‑cause analysis from days to hours, which, in many cases, is what decides whether you miss a production target or not.

Related or Supporting Products

  • ABB RET615 – Compact transformer protection for two‑winding units; good when space is tight and the scheme is simpler.
  • ABB RET630 – More advanced transformer protection with extended I/O and application flexibility for complex schemes.
  • ABB REF620 – Feeder protection; a suitable companion on the HV/LV sides if you standardize on Relion 620.
  • ABB REM620 – Motor protection; useful in the same substation when large MV motors share the process bus.
  • ABB RTXP 24 test switch – Test switch accessory to safely isolate and test circuits during commissioning and maintenance.
  • ABB COM600E – Substation gateway/HMI for IEC 61850 systems if you are building a unified station‑level architecture.

Installation & Maintenance

  • Panel and environment – Mount in a clean, ventilated cabinet per IEC 62271 norms; keep ambient within the stated temperature range and below ~95% RH non‑condensing.
  • Wiring – Use proper CT/VT polarity and earthing practices; segregate power and signal wiring; for Ethernet, use Cat5e/Cat6 shielded where required.
  • Commissioning – Parameterize with PCM600, verify ratio/phase compensation and slope settings for 87T, run secondary injection tests, and validate GOOSE subscriptions if used.
  • Safety – Prove dead, short CT secondaries before disconnection, and follow lockout/tagout. Arc‑safe procedures are recommended during live system tests.
  • Routine maintenance – Review event logs quarterly, export disturbance records after trips, clean the HMI and ventilation paths, and back up configuration. Firmware updates can be applied during planned outages after compatibility checks.
  • Spares – Keeping a spare HMI and a pre‑configured IED on the shelf can cut mean time to restore in many cases.

Quality & Certifications

  • CE‑marked; tested to relevant IEC 60255 standards for protective relays.
  • Produced under ISO 9001 quality management.
  • RoHS compliant; UL/cUL listings apply to many variants (availability can be variant‑specific).
  • IEC 61850 conformance tested; supports GOOSE messaging for station bus applications.

Manufacturer warranty terms apply per ABB policy; our supply is backed by a 365‑day warranty as stated above.