SIMPLEX 4100-3102 | MAPNET II Addressable Interface Module

$3,550.00

Model: 4100-3102

Manufacturer: Simplex (Johnson Controls)

Product Type: MAPNET II addressable interface module

System Compatibility:

Simplex 4100

Simplex 4100U

Categories: SKU: Simplex 4100-3102
contact qrcode

Need help?
Email: sales@fyplc.cn
Tel/WhatsApp: +86 173 5088 0093

Description

The product photos shown are not of the actual items. Please contact sales@fyplc.cn for details.

1. Product Overview

The SIMPLEX 4100-3102 is a MAPNET II addressable interface module designed for use in Simplex 4100-series fire alarm control panels, including the 4100U and 4100ES systems. It functions as a communication interface between the fire alarm control panel (FACP) and field-installed addressable devices such as smoke detectors, manual pull stations, and monitoring modules.

The module enables the fire panel to supervise and communicate with devices connected to the MAPNET II signaling line circuit (SLC). By supporting up to 127 addressable points, it allows large buildings and industrial facilities to connect numerous fire detection devices to a single control system while maintaining reliable monitoring and alarm reporting.

The 4100-3102 is typically installed in the CPU bay or expansion bay of the fire alarm control unit and uses a motherboard and daughter-card architecture to provide stable communication with field devices.

BOMBARDIER-DTCC742A

2. Technical Specifications

Model: 4100-3102

Manufacturer: Simplex (Johnson Controls)

Product Type: MAPNET II addressable interface module

System Compatibility:

Simplex 4100

Simplex 4100U

Simplex 4100ES fire alarm control panels

Maximum Addressable Points: Up to 127 MAPNET II devices

Module Size: 2 slots within the panel expansion bay

Device Loading: Approximately 1.7 mA per MAPNET II device

Current Consumption:

Module only: ~255 mA (supervisory), ~275 mA (alarm)

Fully loaded: ~471 mA (supervisory), ~491 mA (alarm)

Installation: Plug-in module for CPU or expansion bay

Function: Addressable SLC communication interface for detectors and modules

IC698CPE010-JU

3. Key Features and Advantages

Addressable Device Integration
Supports up to 127 addressable field devices, allowing flexible expansion of fire detection networks in large buildings.

MAPNET II Communication Technology
Provides digital communication between the fire panel and detection devices, enabling precise device identification, diagnostics, and alarm reporting.

High System Reliability
Designed for mission-critical life-safety systems, the module ensures continuous monitoring of connected devices and immediate reporting of faults or alarms.

Modular Expansion Architecture
The two-slot plug-in module format allows quick installation and easy replacement inside the fire alarm control panel expansion bay.

Compatible with Legacy MAPNET Systems
The module supports MAPNET II devices and can maintain compatibility with existing installations when upgrading fire alarm systems.

4. Typical Applications

Commercial Buildings
Used in fire alarm control panels monitoring smoke detectors, pull stations, and alarm modules across office buildings, malls, and hotels.

Industrial Facilities
Provides fire detection connectivity for factories, warehouses, and industrial plants requiring addressable fire protection systems.

Hospitals and Public Infrastructure
Ensures reliable fire detection and alarm reporting in critical environments such as hospitals, airports, and transportation hubs.

Large Campus Installations
Allows large networks of fire detection devices to be managed by centralized Simplex 4100-series control systems.