IPSYS01 System Power Module

$2,355.00

  • Product Model: IPSYS01
  • Brand: ABB
  • Warranty: One Year
  • Input Voltage: 102‑264 VAC universal; 102‑144 VDC DC input support
Categories: Tags: SKU: IPSYS01
Lily

Need help?
Email: sales@fyplc.cn
Tel/WhatsApp: +86 153 5945 8915

Description

IPSYS01 System Power Module

Technical Specifications

  • Product Model: IPSYS01
  • Brand: ABB
  • Warranty: One Year
  • Input Voltage: 102‑264 VAC universal; 102‑144 VDC DC input support
  • Operating Temperature: 0 °C to +55 °C
  • Storage Temperature: ‑40 °C to +85 °C
  • Response Time: Not applicable (power supply unit); 20 ms power‑hold‑up time after input loss
  • Protection Class: IP20 (cabinet rack‑mount assembly)
  • Accuracy Class: ±0.5 % line regulation; within‑spec load regulation from 0‑100 % load
  • Output Frequency: Not applicable (DC power conversion)
  • Rated Current Range: Parallel current‑sharing within 5 % deviation between redundant units
  • Communication Interface: Front‑panel LED status indicators; Harmony rack backplane interface
  • Supported Protocols: Internal Harmony rack system bus; status reporting via IPMON01 monitor module
  • Overload Capacity: Built‑in over‑voltage, over‑current and short‑circuit protection; active power‑factor correction >0.95
  • Dimensions: 444.5 mm × 48.3 mm × 218.4 mm

Product Overview

The IPSYS01 is a rack‑mounted system power module for ABB Symphony Plus Harmony Rack I/O DCS platforms, delivering regulated 5 VDC, 15 VDC, ‑15 VDC backplane power to controllers and I/O cards inside the control rack. It accepts both AC and DC main‑supply inputs and supports parallel redundant deployment with active current‑sharing to balance load distribution across multiple power units. Front‑panel bi‑color LED indicators report module health, output status and fault conditions for quick on‑site visual diagnostics.

This power module addresses critical high‑availability control‑system risks: unstable backplane voltages from mains fluctuation, single‑point power‑supply failure, and short‑circuit damage propagating across rack hardware. Redundant configurations allow hot‑swap replacement of one power unit without disrupting running DCS operations. Power‑plant control engineers, DCS retrofit specialists and site‑maintenance teams benefit most. It fits standard Harmony power‑chassis slots, works alongside IPMON01 power‑monitor hardware for remote system‑power alarm reporting, and serves as drop‑in spare hardware for legacy Bailey‑originated DCS installations within power‑generation, water‑treatment and process‑manufacturing facilities.

abb_gdd471a001_2uba002322r0001_motor_control_module


Key Application Notes

  • Supplies system logic voltages for rack‑based I/O and controllers; field‑side 24 VDC I/O power requires separate IPFLD01 / IPFLD24 field‑power modules
  • Mixed AC‑and‑DC input sources are permitted for redundant 2N power‑supply configurations
  • Conformal‑coated PCB variant options are available for cabinets with elevated humidity and airborne‑contaminant exposure
  • Hot‑swap capability only applies in multi‑module redundant power‑supply setups
  • System‑level power‑health status can be forwarded to DCS HMI when paired with IPMON01 monitoring module