Description
ABB AI03 8-Channel RTD Temperature Input Module
The ABB AI03 is an SD series RTD analog input module for Symphony Plus DCS systems, dedicated to temperature measurement with resistance temperature detectors. It supports 2-wire, 3-wire and 4-wire RTD connections, and the AI03 converts resistance signals into digital temperature data for the Symphony Plus control backplane.
Technical Specifications
- Brand: ABB
- Model: AI03
- Channel: 8 group-isolated RTD input channels
- Supported sensors: Pt100 (US & Euro), Ni120, Cu53
- Wiring modes: 2-wire, 3-wire, 4-wire
- A/D resolution: 16 bits with polarity
- ADC layout: 4 converters, 2 channels per ADC
- Update cycle: 450 ms for all 8 channels
- Base unit: xBS01-CJC
- Power supply: 24 VDC
- Operating temperature: -20°C ~ +60°C
- Isolation: Group isolation
- HART function: Not supported
- Mounting: DIN rail installation for SD I/O rack
Key Features Automatic calibration removes the need for regular manual calibration. Each channel can be individually configured for different RTD types via function codes FC221 and FC222. It provides open-circuit detection for broken RTD cables. Group isolation reduces common-mode noise interference from field sensors. Hot-swap capability allows module replacement without shutting down the whole DCS rack. Front LED indicators display channel status and fault alarms for convenient on-site maintenance.
Application Scenarios This RTD input module is widely used in power plants, petrochemical refineries, pulp and paper mills, chemical plants and water treatment facilities. It collects temperature readings from pipelines, reactors, furnaces and bearings for process monitoring, over-temperature protection and closed-loop control.







Reviews