Description
Product Overview
The MTL4532 is a backplane‑mounted three‑port galvanically isolated pulse/frequency interface for hazardous area flow, turbine, encoder, pulse transmitter and NAMUR proximity sensors. It accepts pulse input from zone 0/1/2, delivers simultaneously: solid‑state pulse output, 4–20 mA frequency‑to‑current conversion, plus relay line fault alarm. Fits the CPS16 backplane you queried before.
Technical Specifications
- Brand: Eaton MTL Instruments
- Model: MTL4532
- Warranty: One Year
- Condition: 100% New & Original
- Input: NAMUR proximity, switch, 2/3‑wire pulse transmitter, voltage pulse
- Frequency range: DC to 50 kHz
- Pulse output delay: Max 10 µs
- Analog output: 4–20 mA proportional to input frequency
- Alarm: Relay contact for line fault / LFD
- Isolation: 3‑port isolation (hazardous side / safe side / supply)
- Power: 20–35 VDC bus supply
- Mounting: Plug‑in for MTL CPS16 / CPS16‑CC / CPS16‑PC backplane
- Operating temp: −20 °C ~ +60 °C
- Ex marking: [Ex ia Ga] IIC
- Certificates: ATEX, IECEx, NEPSI
- Indicators: Power, active, fault LED
Differentiation
- MTL4532: Backplane pulse isolator (CPS16 rack)
- MTL5532: DIN‑rail standalone version, same function
- MTL4531: Vibration transducer interface
- MTL4541: 2/3‑wire transmitter repeater
- Origin: United Kingdom
- Lifecycle: Active production spare; commonly used on flow meters, turbine speed pickups, pulse counters in petrochemical and ESD systems







Reviews