HIMA X-DO 32 01 (X-DO3201) 32-channel SIL3 Safety Digital Output Module

$3,560.00

  •  

    Model: X-DO 32 01
    Manufacturer: HIMA (Germany)

  • Operating Temperature:0 ℃ ~ +60 ℃
  • Storage Temperature:-40 ℃ ~ +85 ℃
Categories: Tags: SKU: X-DO 32 01
Lily

Need help?
Email: sales@fyplc.cn
Tel/WhatsApp: +86 153 5945 8915

Description

HIMA X-DO 32 01 (X-DO3201) 32-channel SIL3 Safety Digital Output Module

– Model: **X-DO 32 01**
– Manufacturer: HIMA (Germany)
– Matching System: **HIMax Large Modular SIS Safety Instrumentation System**, used with X-CPU 01 main control CPU and X-AI 32 01 analog input module
– Safety Certification: **SIL 3 (IEC 61508 / IEC 61511)**, ISO 13849-1 PL e, EN 954-1 Category 4, TÜV Rheinland authoritative safety certification

– Warranty: 1 Year

 

1. Core Electrical & Channel Parameters

Output Specifications

  1. Total 32 digital transistor output channels, grouped for fault isolation
  2. Output power:24VDC (18~28.8VDC wide range SELV safety voltage)
  3. Single channel rated load:0.5A DC maximum, short-circuit current limited to 2A per channel
  4. Module total maximum aggregate output current:12A
  5. Load compatibility: Resistive load, inductive solenoid valves, relay coils, indicator lamps, contactors
  6. Non-galvanic internal grouping isolation, matched with dedicated terminal base board for field wiring

Built-in Channel Diagnosis & Protection

  • Per-channel short-circuit, overload, open-circuit wiring continuous monitoring
  • Overcurrent automatic cutoff for individual faulty channel, single point failure does not crash the whole module
  • Periodic pulse self-test on all output circuits to detect internal switch component drift
  • Hardware overvoltage, reverse polarity, EMC surge and ESD protection
  • HIMA_X-DO1201_985210204_3

Safety Redundancy Architecture

Adopts internal 1oo2D dual diagnostic safety circuit

  • Dual path logic voting to eliminate dangerous undetected faults
  • Full cross-check between backplane bus command and actual output state
  • Supports online hot-swap replacement during SIS system running, no safety loop interruption

2. Environmental & Mechanical Data

  • Protection Class:IP20 (only installed inside indoor control cabinet)
  • Operating Temperature:0 ℃ ~ +60 ℃
  • Storage Temperature:-40 ℃ ~ +85 ℃
  • Ambient Humidity:5% ~ 95% RH non-condensing
  • Form Factor:Standard HIMax 6U Eurocard rack plug-in module
  • Net Weight:Approx. 0.95 kg
  • Mounting:Lockable front screw anti-vibration fixation on X-BP series backplane
  • Front Panel Indicators:Power RUN, Module General Fault, Backplane Bus Error, Group Channel Fault LED lights

3. Product Overview

The X-DO 32 01 is the high-density execution terminal of the HIMax SIS safety system. After the X-CPU 01 safety CPU completes safety logic judgment, this module converts internal digital safety commands into 24VDC field driving signals to trigger all safety executive actuators.

In ESD emergency shutdown, F&G fire & gas protection and HIPPS high-integrity pressure protection loops, it undertakes core safety actions: tripping shutdown solenoid valves, closing emergency isolation shutoff valves, cutting fuel/gas supply, tripping turbine trip coils, stopping compressors, activating fire suppression systems and alarm horns.

Reviews

There are no reviews yet.

Be the first to review “HIMA X-DO 32 01 (X-DO3201) 32-channel SIL3 Safety Digital Output Module”

Your email address will not be published. Required fields are marked *

zzfyplc_Lily

Related products