Description
Metso D200136 (ADC5483‑D200136) DCS System Power Supply Module
Technical Specifications
- Product Model: D200136;Alternative Code: ADC5483‑D200136
- Brand: Metso (Valmet DNA System)
- Warranty: One Year
- Input Voltage: 115‑230 VAC universal single‑phase, 50‑60 Hz
- Operating Temperature: 0 °C ~ +55 °C DIN‑rail cabinet‑mount
- Storage Temperature: ‑40 °C ~ +85 °C
- Response Time: Output stabilization<100 ms after power‑on
- Protection Class: IP20, pollution degree 2 for indoor cabinet installation
- Accuracy Class: Output voltage regulation ±1 % FS
- Output Frequency: DC power output, no AC frequency
- Rated Output: 28 VDC, 9 A continuous output rating
- Input Rated Current: 4.5 A @115 VAC; 2.5 A @230 VAC
- Protection Functions: Over‑voltage, under‑voltage, short‑circuit, over‑temperature, overload shutdown
- Indicators: Power ON LED, fault alarm LED status indicators
- Mounting: Standard DIN‑rail mounting, metal enclosed housing
- Dimensions: 185 mm × 130 mm × 70 mm
- Weight: approx 2.1 kg
Product Overview
The D200136 (ADC5483‑D200136) is a high‑power DIN‑rail power supply unit for Metso Valmet DNA distributed control system. It converts universal 115/230 VAC mains input into stabilized 28 VDC output, supplying power for DNA series DPU controllers, analog and digital I/O modules within control cabinets. It provides comprehensive hardware‑level fault protection, and visual LED status indication for power‑ok and alarm conditions to simplify on‑site troubleshooting. Robust metal housing improves vibration resistance and heat dissipation, delivering stable power output in pulp‑and‑paper, mining and power‑plant dusty cabinet environments. D200136L is the later hardware revision variant of this unit.
This power supply addresses DCS cabinet power‑supply challenges: wide‑range universal AC input, high 9 A DC output capacity, integrated multi‑fault protection, drop‑in spare‑part compatibility for legacy DNA‑series retrofit‑maintenance projects. Process‑automation engineers, pulp‑and‑paper and mineral‑processing‑plant maintenance technicians and retrofit integrators benefit most. Typical applications: paper‑machine DCS control cabinets, mineral‑processing plant distributed‑I/O power feeding, power‑plant auxiliary DCS system power supply.
Key Application Notes
‑Power‑supply unit; cannot operate standalone. Requires compatible AC mains input and Metso DNA DCS system hardware load. ‑D200136 and D200136L are different hardware revisions; full part‑number matching is required for replacement substitution. ‑Not hot‑swap capable: Cut off AC input power completely before installation or removal. ‑Original OEM production discontinued; aftermarket surplus/refurbished spare‑parts are widely circulated for legacy‑DCS maintenance. ‑Respect output‑current derating rules when ambient temperature exceeds 45 °C. ‑Follow Metso ADC5483‑D200136 hardware manual for AC input wiring, load‑capacity calculation and fault‑diagnostic procedures.