Description
FIREYE 95DSS2-1 Dual UV/IR Integrated Flame Scanner – Multi-Fuel Combustion Safety Monitor
Core Product Specifications
- Brand: FIREYE
- Model: 95DSS2-1 (S2 enhanced version)
- Availability: In Stock
- Delivery Time: Within 3 working days after payment confirmation
- Guarantee: 12 months warranty
- Condition: Brand New Original
- Power Supply: 24VDC, 0.35A standard industrial control power
- Dual Sensor Spectrum:
UV channel: 295~320nm ultraviolet; IR channel: 700~1700nm infrared InGaAs sensor
- Signal Output:
SPST flame relay (NO); SPST fault relay (NC); 4–20mA analog flame intensity output (max load 750Ω)
- Operation Interface: 8-character alphanumeric LED display + 4-key local keypad
- Self-Check Mode: Electronic E-Scan continuous self-test, no mechanical shutter design
- Operating Temperature: -40°C ~ +65°C; relative humidity 0~95% non-condensing
- Protection Grade: IP65 standard housing; explosion-proof variant 95DSS2-1CEX reaches ATEX EEx d IIC T6, IP66
- Mounting: Standard 1-inch NPT burner flange mounting, quartz sight window
- Communication: Support Fireye PC upper computer software remote parameter reading & tuning
- Storage Preset: 4 groups of independent flame parameter storage files, fast switch for multi-burner units
Key Features & Advantages
- UV+IR Dual-Spectrum Compound Flame Recognition
Dual-channel synchronous detection logic distinguishes real combustion flame from furnace wall high-temperature radiation, sunlight, electric arc interference. Perfect compatible with all single/mixed fuel (natural gas, diesel, heavy oil, pulverized coal), solving single UV/IR probe false trip defects under complex furnace conditions.
- S2 Auto-Tune Intelligent Calibration Function
Built-in AutoTune automatic matching algorithm, 21 optional flame flicker frequency bands, one-click automatic locking optimal gain and threshold; manual override adjustment reserved for special furnace working conditions, greatly shortening field commissioning time.
- Shutter-Free Electronic Continuous Self-Diagnosis
E-Scan electronic self-test runs 24/7 without mechanical moving parts, monitors sensor aging, lens pollution, internal circuit faults in real time, outputs fault contact signal immediately, reducing periodic maintenance frequency and mechanical failure risks compared with traditional shutter self-check probes.
- All-In-One Integrated Design Simplifies Wiring
Internal flame relay eliminates external amplifier module; front local display and keypad support on-site threshold modification, flame strength value real-time viewing without laptop; 4–20mA analog signal directly connected to DCS/PLC for centralized flame strength trend monitoring.