Description
Emerson EPRO MMS6410 Dual Channel Displacement Measuring Amplifier Module
Technical Specifications
- Model: MMS6410
- Brand: EPRO (Emerson Germany), MMS6000 Turbine Supervisory Instrument (TSI) system series
- Warranty: One Year
- Power Supply: 24 VDC industrial control power, max power consumption 3W
- Operating Temperature: -20℃ ~ +60℃
- Storage Temperature: -40℃ ~ +85℃
- Protection Class: IP20 circuit board, installed inside 19-inch standard control cabinet
- Measurement Performance
- Dual fully independent measuring channels, support sum/difference mathematical operation of two channels
- Frequency response: 0 ~ 100Hz (-3dB), for static and dynamic displacement signals
- Carrier frequency: 4.75kHz, sensor excitation output 4Vrms
- Input impedance: 200kΩ, differential isolated input with short/open circuit protection

- Sensor Compatibility: Matches EPRO PR9350 series inductive eddy current sensors (half-bridge / full-bridge / differential transformer), for shaft axial displacement, differential expansion, cylinder thermal expansion measurement
- Signal Output: Each channel with isolated 4–20mA current output and ±10V voltage analog output; rear optocoupler pre-alarm/main alarm relay dry contact
- Communication Interfaces
- Front RS232 local port for parameter calibration, zero point trimming and firmware upgrade
- Rear RS485 EPRO proprietary bus, upload data to MMS6824 gateway module for Modbus conversion
- 1P/RPM speed pulse input for rotor speed auxiliary collection
- Overload Protection: 2kV isolation between power, sensor loop and communication bus; built-in sensor break, overvoltage, overtemperature and watchdog self-diagnosis
- Mechanical Dimension: Single-slot Eurocard plug-in PCB, net weight approx 300g, matches MMS6000 rack chassis







Reviews