Description
Product Overview
The 3VL8716-1TH40-0AA0 is a SENTRON VL1600N molded case circuit breaker: a 4-pole, 1600 A frame device with an electronic ETU22 trip unit providing L-S-I-G protection — overload, short-time delayed short circuit, instantaneous short circuit and earth fault. Because the trip unit is electronic rather than thermal-magnetic, the overload threshold is adjustable from 640 A to 1600 A on site, which lets one frame size serve several feeder ratings and lets protection be re-set when a load changes instead of replacing the breaker. The 4-pole version with neutral protection suits three-phase four-wire distribution where the neutral must be supervised, and the 55 kA breaking capacity at 415 V AC covers incoming and sub-main feeder duty in industrial switchboards. Typical use is main or sub-main protection in a SIVACON-style distribution board, protecting transformers, generator feeds and large machine groups — the fixed-mounted, front-connected design keeps the busbar and cable termination scheme simple in an existing panel being maintained.
Technical Specifications
- Brand: Siemens (SENTRON)
- Model: 3VL8716-1TH40-0AA0
- Product Type: Molded case circuit breaker (MCCB), system/installation protection
- Frame / Size: VL1600N, size 3VL8, performance class N (standard breaking capacity)
- Poles: 4-pole, neutral protected
- Rated Current (In): 1600 A
- Trip Unit: Electronic ETU22, LSIG function
- Overload Protection (L): Ir adjustable 640–1600 A
- Short-time Delayed Short Circuit (S): Isd adjustable 1.5–8 x Ir (2400–12800 A), with time delay
- Instantaneous Short Circuit (I): Ii = 9 x In (14400 A, fixed)
- Earth Fault Protection (G): Integrated in ETU22, adjustable with OFF setting
- Breaking Capacity (Icu): 65 kA at 240 V AC; 55 kA at 415 V AC; 35 kA at 440 V AC; 25 kA at 500 kA rating point; 20 kA at 690 V AC
- Service Breaking Capacity (Ics): 35 kA at 240 V; 28 kA at 415 V; 20 kA at 500 V; 10 kA at 690 V
- Rated Voltage / Frequency: Up to 690 V AC, 50/60 Hz; utilization category A
- Input / Output (main circuit): Front-side main conductor connection, fixed-mounted built-in device; 3-phase + N power circuit; no integrated auxiliary contacts, no auxiliary release, no alarm switch fitted
- Current Derating: 1600 A up to 50 °C; 1488 A at 55–60 °C; 1376 A at 65–70 °C
- Mechanical / Electrical Endurance: 3000 mechanical operating cycles, 1500 electrical operating cycles (typical); max. operating frequency 30 1/s
- Operating Temp: Ambient per IEC 60947 at rated current up to 50 °C (see derating); UL 489 rating referenced at 40 °C
- Protection: IP20 (device, open front)
- Mounting: Fixed-mounted in switchboard / enclosure, front connection; not DIN rail mounted
- Dimensions / Weight: Approx. 42.0 kg
- Warranty: One Year
- Condition: 100% New & Original
Key Notes
- The trip unit is the configurable part: Ir, Isd and the G threshold must be set to the protection study before energising. Out of the box it does not match a specific feeder.
- This variant carries no auxiliary contacts, shunt release or alarm switch — those are separate accessories. If the panel’s interlocking or remote-tripping scheme relied on them, they must be ordered and fitted.
- The 3VL87 series is discontinued by the manufacturer; for new installations the current 3VA platform is the replacement path, so treat this unit as a form-fit-function spare for existing VL1600 panels.
- The 4-pole neutral protection setting and the 42 kg mass mean two-person handling and a checked busbar torque sequence at installation.







Reviews