Description
GE Fanuc) IC695ETM001 Ethernet Interface Module
Technical Specifications
- Product Model: IC695ETM001
- Brand: Emerson / GE Fanuc
- Warranty: One Year
- Power Supply: Powered via RX3i PLC internal universal backplane
- Operating Temperature: 0°C ~ +60°C
- Storage Temperature: -40°C ~ +85°C
- Response Time: Wire-speed data forwarding, low-latency industrial communication
- Protection Class: IP20, single-slot plug-in module for PACSystems RX3i rack
- Accuracy Class: Not applicable (Industrial Communication Module)
- Communication Interface: 2×10/100Base-T(X) shielded RJ45 ports (integrated internal switch); 1×RS232 Station Manager diagnostic port
- Supported Protocols: SRTP, Modbus TCP Client/Server, EGD (Ethernet Global Data), TCP/IP, SNTP time synchronization
- Special Features: Hot-swappable; redundant IP addressing support; built-in LED status indicators
- Overload Protection: ESD & surge protection for Ethernet ports, module self-diagnosis function
- Dimensions: 136 mm × 130 mm × 54 mm

-
Product Overview
The IC695ETM001 is an Ethernet communication module designed for Emerson PACSystems RX3i PLC systems. Equipped with dual auto-sensing 10/100Mbps Ethernet ports with embedded switch, it supports daisy-chain network topology to connect HMIs, engineering workstations, SCADA servers and peer controllers.The module enables program downloading, real-time peer-to-peer data exchange via EGD protocol, and Modbus TCP communication with third-party field devices. The dedicated RS232 Station Manager port provides local diagnostic access. Hot-swap capability allows replacement without shutting down the PLC system, minimizing production downtime. Automation engineers and maintenance technicians widely adopt this module for new cabinet construction and spare part replacement for legacy RX3i control systems.
Application Scenarios
- Continuous Process DCS Auxiliary Control Cabinets: Build control network for RX3i PLCs, realizing data interaction between field controllers and central SCADA systems.
- Automated Assembly & Packaging Production Lines: Interconnect distributed PLC stations, servo drives and touchscreen HMIs to achieve coordinated equipment operation.
- Water & Wastewater Treatment Plants: Transmit measurement data and control commands between remote pump stations and main control room.
- Thermal & Renewable Power Plant Auxiliary Systems: Deployed on boiler, chemical water and ash handling control PLCs for stable unattended network communication.